Welcome to visit:Tianjin Xindele Technology Co., LtdOfficial website!
Product Display

Fire Smoke Exhaust Fans

Fire smoke exhaust fans remove smoke and heat during a building fire, creating conditions for evacuation and firefighting. Standards require these fans to keep running in hot smoke for a specified period, which makes high-temperature capability the first selection criterion.

SINDFAN smoke exhaust fans are designed for high-temperature duty and cover the common requirements of 250°C/1h and 300°C/2h. Impellers are cast aluminium LM6 (high-temperature type) or stainless steel, with high-temperature motors and bearings, and treated casings. Both exhaust and make-up air duty can be selected.

Key specifications

Impeller diameterØ250 - Ø1800mm
High temperature rating250°C/1h, 300°C/2h, 400°C/1h (by project fire requirement)
Impeller materialCast aluminium LM6 (high-temperature type) / stainless steel for corrosive or very high temperature duty
MotorHigh-temperature motor, class F insulation, IP55 or better
CasingMild steel 2 - 5mm, hot-dip galvanised or corrosion-protective coating
BalancingISO 1940-1 G6.3
TestingAMCA 210-07, ISO 5801
AccessoriesSilencer, anti-vibration mounts, guard, terminal box

Figures above are our standard ranges; the actual supply is per the agreed technical specification. Impeller performance curves describe the bare impeller under standard inlet conditions. Once installed, performance is affected by casing clearance, tip clearance, inlet straightening and guide vanes; tested as a complete fan to GB/T 1236 / AMCA 210 the result typically differs by 2-5%. Site measurement governs and no complete-fan performance warranty is implied.

Typical applications

  • High-rise and mixed-use building smoke exhaust
  • Underground car park smoke exhaust and make-up air
  • Metro station and running tunnel smoke control
  • Hospitals, schools and shopping centres
  • Industrial plant smoke exhaust and process heat removal
  • Tunnel and utility tunnel fire smoke control
  • Machine room and switch room emergency exhaust

Selection notes

  • The high-temperature rating must match the design drawing: 250°C/1h and 300°C/2h differ significantly in cost, so any low-price offer must state the rating to avoid failing acceptance.
  • Treat exhaust and make-up air as a pair: exhausting without supplying make-up air reduces the effective exhaust rate, so calculate the make-up path and volume together.
  • Bearings and motors are the weak points at temperature - always specify high-temperature components. A standard motor fails within minutes at 250°C.
  • Building smoke exhaust products need CCCF in China; where we supply the impeller or fan body only, certification is handled by the fan builder or the project.

FAQ

What is the difference between 250°C/1h and 300°C/2h?

The temperature rating: 300°C/2h demands high-temperature motors, high-temperature bearings and stricter material selection, and costs more. Select to the fire class on the design drawing and do not downgrade it.

Can I buy the impeller only?

Yes. We can supply cast aluminium or stainless steel impellers to the high-temperature requirement with performance curves; unit certification is handled by the project or the fan builder.

Can it be two-speed or inverter driven?

Yes. Where smoke duty and normal ventilation run at different speeds, two-speed motors or VFD control are common. State the flow and pressure for both duties when ordering.

How is tip clearance confirmed?

Tip clearance between impeller and casing drives both efficiency and safety, and thermal expansion matters at high temperature. The casing bore should be provided by the fan builder and we supply to the matching tolerance.

Need a selection or a quotation? Send us air volume, total or static pressure (please state which), medium temperature and quantity, and we will reply within 24 hours. Contact details are at the foot of this page.