A contra-rotating fan has two impellers turning in opposite directions. The swirl generated by the first stage is recovered by the second, giving higher pressure and flow for the same diameter, with a short axial length and no guide vanes. It is the workhorse for mine auxiliary ventilation and long-distance air delivery.
SINDFAN contra-rotating units are designed to mine auxiliary fan practice: two motors driving directly on their own shafts, no inter-stage duct, impellers replaceable as assemblies. We can also supply the two impeller stages separately.
| Impeller diameter | Ø400 - Ø1250mm (typically Ø600 / Ø630 / Ø800) |
|---|---|
| Stage arrangement | Two stages, counter-rotating, e.g. 7+6 blade combination |
| Motors | 2 x 18.5kW to 2 x 37kW, direct on shaft |
| Air volume | approx. 5 - 12 m³/s depending on model and blade angle |
| Total pressure | 3000 - 4000 Pa class depending on model |
| Blade material | Cast aluminium or fabricated steel |
| Air delivery distance | Ø600 ducting approx. 300m (400m maximum); Ø800 ducting approx. 600-800m (1000m maximum) |
| Mounting | Rail bogie for underground use / fixed base (optional) |
Figures above are our standard ranges; the actual supply is per the agreed technical specification. Impeller performance curves describe the bare impeller under standard inlet conditions. Once installed, performance is affected by casing clearance, tip clearance, inlet straightening and guide vanes; tested as a complete fan to GB/T 1236 / AMCA 210 the result typically differs by 2-5%. Site measurement governs and no complete-fan performance warranty is implied.
More pressure for the same diameter in a shorter axial length, because the second stage recovers the swirl loss of the first - two stages of work for one compact body.
Standard units reach the 3000-4000 Pa total pressure class. Higher pressure requires re-calculating diameter, speed and blade count - send us the duty point.
Ø800 ducting delivers 600-800m reliably (about 1000m maximum); Ø600 ducting about 300m. Actual performance depends on duct quality, joint leakage and the number of bends, so acceptance testing should use the conservative figure.
Need a selection or a quotation? Send us air volume, total or static pressure (please state which), medium temperature and quantity, and we will reply within 24 hours. Contact details are at the foot of this page.